Abstract

This research investigates the harmful effects of changes in condenser seawater coolant temperature, fouling, and salinity, on the thermal performance of an existed CANDU nuclear power plant (NPP). A mathematical model is developed to relate seawater cooling temperature, fouling, and salinity to the output power and thermal efficiency of the plant. The model also elaborates the impact of the condenser performance on power and efficiency. The thermal efficiency of the considered CANDU NPP is reduced by 2.24%, for combined extreme increases in the condenser cooling seawater temperature, fouling factor of seawater and treated boiler feed water, and salinity of 10 °C, 0.0002, 0.00001 m2K/W, and 100 g/kg, respectively. A rise in the condenser efficiency from 40 – 100 % increases the output power by 7.0136 % of the plant, and the thermal efficiency increases by about 2.34 %.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.