Abstract
Abstract An internal heat exchanger (IHX) is often used to improve the coefficient of performance (COP) of CO 2 inverse cycles. This paper presents a detailed analysis of the IHX’s effect in CO 2 inverse cycles and finds suitable operating conditions for the IHX from a thermodynamic performance point of view. The results indicate that the COP is slightly reduced by an IHX in a CO 2 subcritical inverse cycle, so an IHX is not justified. However, for transcritical CO 2 inverse cycles, the compressor discharge pressures and CO 2 gas cooler outlet temperatures both have significant impacts on system performance. The analysis results for transcritical CO 2 inverse cycles show that a transition discharge pressure and a transition CO 2 gas cooler outlet temperature are objective existence above which the IHX improves the cycle performance.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.