Abstract
The use of water mist to extinguish fire is a problem of particular interest since the banning of halogen-based agents for environmental reasons. This interest is reflected in the large number of researches performed on the main fire-extinguishing mechanisms of water mist: heat extraction, oxygen displacement and attenuation of heat fluxes. In contrast, there are still little known about the chemical and some other aspects of water mist addition on the pool fire. In this paper, a phenomenological study was conducted of the effect of water mist addition on the kerosene pool fire through the measurement of the heat release rate, CO, CO2 and O2 species concentration in combustion. The experimental results show that there is a significant enhancement effect at the beginning stage of water mist addition. Then, the flame size was decreased abruptly. By physical suppression effect combined with chemical effect, the experiments’ results are explained especially. The study of effects of water mist on pool fire will be useful for optimizing designation of water mist fire-suppression system, improving the fire suppression efficiency and extending their application field.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.