Abstract

The conventional fault analysis method based on symmetrical components supposes that the three-phase parameters of un-transposed transmission line are symmetrical in case of fault. The errors caused by the method with the symmetrical distributed parameter circuit model as the equivalent circuit of the un-transposed ultra high voltage(UHV) transmission line were studied under both normal operation and fault, and the corresponding problems arising were pointed out. By contrast with electromagnetic transient and power electronics(EMTPE) simulation results with the asymmetrical distributed parameter circuit model of un-transposed line, it is shown that the conventional method cannot show the existence of negative and zero sequences before fault happening and there are many errors on voltage and current after fault happening which are different with fault types. The error ranges of voltage and current are 2.13%–81.13% and −7.82%– −86.15%, respectively.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.