Abstract
This paper presents a study on the performances of distance relays setting in 400 kV in Eastern Algerian transmission networks at Sonelgaz Group (Algerian Company of Electricity) compensated by shunt Flexible AC Transmission System (FACTS). The facts are used for controlling transmission voltage, power flow, reactive power, and damping of power system oscillations in high power transfer levels. The direct impacts of SVC devices i.e. Thyristor Controlled Reactor (TCR) and the Thyristor Switched Capacitors (TSC) insertion, on the total impedance of a transmission line (<i>Z</i><SUB><i>AB</i></SUB>) protected by MHO distance relay are investigated. The modified setting zones protections (<i>Z</i><SUB><i>1</i></SUB>, <i>Z</i><SUB><i>2</i></SUB> and <i>Z</i><SUB><i>3</i></SUB>) have been calculated in order to improve the performances of distance relay protection and prevent circuit breaker nuisance tripping. The simulation results are performed in MATLAB software and show the direct impact of the thyristors firing angle (<i>α</i>) on the total impedance of the protected line.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.