Abstract

This study measured ventilation volumes and particle concentrations in indoor environments with open windows and doors. In addition, the effect of the airflow mode of the air conditioner on the ventilation volume and indoor particle concentration variations was also measured. The ventilation fan could only provide approximately 43% of the ventilation volume during the design phase. The amount of ventilation differed depending on the opening area in windows and doors. The ventilation volume was increased by opening multiple windows or doors, even when the area of the opening was the same. No significant change in the ventilation rate was observed, although the air conditioner was expected to promote the ventilation rate in the room when set on blow mode. It was confirmed that both 0.3 and 1 μm particles could enter through the gaps around the windows and doors. Although most of the 5 μm particles were from the outdoor air, when the air conditioner was operated in airflow mode, the removal of 5 μm particles was performed by the air conditioner filter. The use of medium-performance or HEPA filters is expected to remove smaller particulates.