Abstract

This study evaluates the effects and consequences of fire-fighting operations on the main characteristics of a fully-developed compartment fire. It also presents data and evaluation of the conditions to which fire-fighters are exposed. A typical room enclosure was used with ventilation through a corridor to the front access door. The fire load was wooden pallets. Flashover was reached and the fire became fully developed before the involvement of the fire-fighting team. The progression of the fire-fighters through the corridor and the main-room suppression attack – in particular the effect of short, medium and long water pulses on either the hot gas layer or the fire seat – was charted against the compartment temperatures, heat release rates, oxygen levels and toxic species concentrations. The fire fighting team was exposed to extreme conditions, heat fluxes in excess of 35kW/m2 and temperatures of the order of 250°C even at crouching level. The fire equivalence ratio showed rich burning with high toxic emissions in particular of CO and unburnt hydrocarbons very early in the fire history and a stabilisation of the equivalence ratio at about 1.8. The fire fighting operations made the combustion temporarily richer and the emissions even higher.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.