Abstract

The effects of external heat radiation on combustion and toxic gas release characteristics of flame retardant cables, which were XLPE insulated, flame retardant PVC sheathed and steel armoured cables, were investigated. The combustion characteristics of the level A and the level C flame retardant cables were explored by the cone calorimeter. For the level C cables, heat release rate (HRR) and CO concentration in cable fires increased and the ignition time decreased with increase of the external radiation heat flux. For level A cables, the HRR and CO concentration showed two-stage variations with the external radiation heat flux. When the external radiation heat flux was smaller than 35 kW/m2, the cable self-extinguished quickly after the ignition. When the external radiation heat flux was larger than 50 kW/m2, the cables showed continuous burning phenomena after the ignition. The level A cable had smaller HRRs compared with that of the level C cable under the same external radiation heat flux. However, the CO concentration of level A cable was remarkably higher than that of the level C cable in the present study. The high CO release rate of cable with well flame retardant ability under large external radiation heat flux requires more caution in the cable fires.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call