Abstract

In order to optimize the thermal-hydraulic performance of a nanofluid-cooled zigzag miniature heat sink (MHS), six different pin-fin interruptions are proposed in the present experimental study. The obtained results show that interrupting the pin-fins has meaningful influences on heat transfer and pressure drop characteristics of the zigzag MHS. For instance, replacing the interrupted MHSs with the basic configuration, i.e. integral MHS, varies the overall heat transfer coefficient in the range of −19% to +23%. At the studied ranges, the maximum value of overall heat transfer coefficient is found as 15,255W/m2K at the mass flow rate of 0.02kg/s corresponding to a specific interrupted MHS. It is detected that all the interrupted MHSs have lower values of the pressure drop in comparison with the integral MHS. It is also found that the cooling performance of the nanofluid-cooled MHSs is greater than the water-cooled MHSs. Finally, the obtained results in the current work may have considerable practical significance as it relates to the design of efficient MHSs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.