Abstract

To achieve an energy sector independent from fossil fuels, a significant increase in the penetration of variable renewable energy sources, such as solar and wind power, is imperative. However, these sources lack the inertia provided by conventional thermo-electric power stations, which is essential for maintaining grid frequency stability. In this study, a grid resembling Madeira Island’s power generation mix was modeled using the Matlab/Simulink platform. The model included solar, wind, hydro, and thermo-electric generation to accurately represent the energy landscape of Madeira Island. Three scenarios were examined: one reflecting the current power generation on Madeira Island, a future scenario with a substantial rise in the percentage of photovoltaic (PV) generation, and the same future scenario but incorporating a battery energy storage system (BESS). Various analyses were conducted to assess the impact on frequency stability during a ground fault and rapid load/generation changes. In the future scenario without a BESS, the thermoelectric power plant generator desynchronized, leading to system collapse in several simulations. However, with the addition of a BESS, a significant improvement in frequency stability was observed. The thermoelectric power plant generator could return to a steady state after each disturbance. Furthermore, both the maximum frequency deviation and the absolute value of the Rate of Change of Frequency (ROCOF) were reduced, indicating enhanced system performance and stability.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call