Abstract

AbstractThe use of mechanically stabilized earth (MSE) retaining walls has gained popularity as an alternative to conventional cast-in-place concrete walls. The construction of MSE walls is cost effective, requires less site preparation, and is technically more feasible compared with conventional concrete retaining walls. However, use of backfill with high fine content and poor drainage behavior can cause excessive wall movement or even failure. The current paper presents the case study of a MSE wall located at State Highway 342 in Lancaster, Texas. The top of the MSE wall has moved as much as 300–450 mm only 5 years after construction. An extensive site and laboratory investigation testing program was conducted to determine the possible causes of the MSE wall movement. The site investigation included soil test boring and resistivity imaging (RI). Perched water zones were identified at a few locations in the backfill area using RI. The bulging of the MSE wall facings was observed where the perched water z...

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.