Abstract

On the basis of a voltage compensation type active superconducting fault current limiter (SFCL) proposed in previous work, the effects of this type SFCL on distance relay protection are studied in this paper. Under the condition that the active SFCL is placed behind the relay element, its current-limiting impedance will be added into the measured impedance between the relay and the fault points. As a result, in order to prevent the refused operation of the relay, the measured impedance should be revised. According to the three different operation modes of the active SFCL, we present the corresponding three modified formulas. Furthermore, using MATLAB, the model of the dual-source power system with the active SFCL is built, and the impacts of the active SFCL on the distance relay protection are studied in detail under the different current-limiting modes and fault distances. The simulation results show that: without using the modified formulas, the introduction of the active SFCL will reduce the protection distance of the relay, and in the case that the modified formulas are adopted, the three modes of the active SFCL will not affect the measured impedance of the relay, and further the validities of the proposed modified formulas can be testified.