Abstract

For a large Spent Fuel Pool (SFP) loss of coolant accidents, properly sized SFP spray can slowdown or possibly preclude fast heat-up of spent fuel. The MELCOR 2.1 model of NPP Krsko pool was developed and tested for cases of loss of cooling accidents. The simple spray system with spray nozzles distributed at specified location at the top of the pool was added to the model. Different loss of coolant rates where studied for different fuel heat loadings, and different openings and flow rates of the spray nozzles. Traditionally, spray nozzles able to produce larger diameter droplets are used close to the fuel locations with higher heat loadings. According to preliminary results, spray nozzles that will be installed are able to limit or delay long-term heat-up of the spent fuel, but in the case of late actuation it is possible to have temporary high oxidation rates and corresponding production of hydrogen.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.