Abstract
We report our ten-year experience of hyperchlorination, thermal shock, chlorine dioxide, monochloramine, boilers and point-of-use filters for controlling legionella contamination in a hospital hot water distribution system. Shock disinfections were associated with a return to pre-treatment contamination levels within one or two months. We found that chlorine dioxide successfully maintained levels at <100 cfu/L, whilst preliminary experiments gave satisfactory results with monochloramine. No contamination was observed applying point-of-use filters and electric boilers at temperatures of >58°C and no cases of nosocomial legionellosis were detected in the ten-year observation period. Our performance ranking in reducing legionella contamination was filter, boiler, chlorine dioxide, hyperchlorination and thermal shock. Chlorine dioxide was the least expensive procedure followed by thermal shock, hyperchlorination, boiler and filter. We suggest adopting chlorine dioxide and electric boilers in parallel.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.