Abstract

We aimed to evaluate the performance of ceiling-mounted UV-C lamps. This study was conducted in an empty room with UV-C lamps in the biocontainment unit of a tertiary care hospital in South Korea. Each pathogen (Staphylococcus aureus, Escherichia coli, Candida krusei, Bacillus cereus, and Mycobacterium peregrinum) was inoculated on blood agar plates and placed in 20 selected places from the UV-C lamp, and irradiation was applied for 15 min. As a control group, the bacterial solution was diluted 10,000 times and UV was not applied. A mean ± SD of 5.95 ± 0.91 log reduction was observed with UV irradiation compared with the control. The log reduction was greatest for S. aureus [median, 7.05 (IQR, 6.49-7.26)] and least for M. peregrinum [median, 4.88 (IQR, 4.58-5.24)]. The degree of log reduction was inversely proportional to the square of the distance from the UV-C lamp (R2 = -0.12, P<.001). In this study, ceiling-mounted UV-C demonstrated effective disinfection of at least 4-log reduction of the test organisms within a 4-m distance. Mounted UV-C lighting is a considerable option for improving surface disinfection.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.