Abstract

A simulation program based on a control volume analysis has been used in the evaluation of the (e, NTU) relationship for coils of complex geometry and flow arrangement. The simulation program has been evaluated through simple geometry and flow arrangement coils. The program results compare very well with correlations for simple cross flow coils, and a number of rows up to four. It has also been determined that closed form correlations developed for coils of an infinite number of tube rows are inadequate for those with number of rows in the range between 5 and 10. In addition, it has been found that closed form (e, NTU) correlations for cross flow coils with the same tube arrangement and number of rows might lead to inaccuracies higher than 10% in the evaluation of the effectiveness of coils of complex flow arrangement.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.