Abstract

Wide-band oscillation arising in grid-connected doubly-fed induction generator (DFIG) systems became increasingly prominent. To address this problem, a stability criterion for wide-band oscillation of power grid-connected DFIG system is proposed based on effective open-loop process (EOP) theory. First, the coupled multi-input multi-output (MIMO) model of grid-connected DFIG system is established based on synchronous reference frame (SRF). Second, the reference frame of grid-connected DFIG system model is transformed by linear transformation, and then the transformed MIMO system is decoupled into two decoupled single input single output (SISO) systems using EOP theory. The mathematical expression of system's stability criterion is derived based on the equivalent SISO models. Finally, the correctness of the proposed stability criterion is validated by time-domain simulation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.