Abstract

This letter proposes a simple and effective hold-up time extension method for server power systems, in which the fan is only turned off during the hold-up time with ac input loss. Due to the elimination of the fan power in the proposed method, the efficiency of the dc-dc converter increases during the hold-up time; thus, the energy stored in the link capacitor decreases less sharply, compared with the conventional method. That is, the hold-up time can be extended without additional devices, volume increase, and operational change of the dc-dc converter, maintaining high efficiency and high power density. The effectiveness of the proposed method is verified by a prototype with 90-264 V <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">ac,rms</sub> input, 800 W/12 V output specifications of the server power supply.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.