Abstract

The American Association of States Highway and Transportation Officials (AASHTO) Test Method T277--Rapid Determination of the Chloride Permeability of Concrete and the American Society of Testing and Materials (ASTM) C1202--Electrical Indication of Concrete's Ability to Resist Chloride Ion Penetration have specified a rapid test method to rank the chloride penetration resistance of various concretes by applying a potential of 60 V DC to a concrete specimen and measuring the charge passed through the specimen during 6 hours of testing. The method is essentially a measurement of electrical conductivity of concrete, which depends on both the pore structure and the chemistry of the pore solution. Analyses based on published results have indicated that the replacement of portland cement with supplementary cementing materials, such as silica fume, can reduce the electrical conductivity of concrete more than 90% because of the change in pore solution composition in the concrete. Chemical composition of pore solution has little to do with the transport of chloride ions in the concrete; thus, it is not correct to use passed charge to rank the chloride penetration resistance of concrete made with supplementary cementing materials.