Abstract
Composite insulators have been used in power system for more than 20 years in China. Compared to porcelain and glass insulators, the pollution flashover performance of composite insulators is better, whereas the icing flashover performance is worse. Shed configuration is a key factor that influences flashover voltage of composite insulators covered ice or snow in icing regions. The DC flashover tests of artificially ice-covered 110 kV composite insulators with different shed configuration were carried out in the multi-function artificial climate chamber. The test results revealed that there are huge differences between the icing flashover voltages of the composite insulators with different shed configuration. The test results indicate that icing flashover performance of the improved composite insulators for icing regions is not always superior to that of the standard composite insulators.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IEEE Transactions on Dielectrics and Electrical Insulation
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.