Abstract

In order to investigate the influence of puffer volume V/sub P/ and operating force to dielectric performance of GCB at current interruption, we calculated the prospective dielectric withstand voltage V/sub W/ between arcing contacts. The withstand voltage was calculated by the electric field strength appeared on arcing contacts and the allowable electric field strength E/sub W//sup */ of hot gas due to thermal puffer action. We could clarify that large initial puffer volume V/sub P/ can increase withstand voltage V/sub W/ at current breaking point and also that an optimum point exists in operating force F. For example, it was found that in case of the operating force of 1000 kgf, the puffer volume V/sub P/ of 1.2 liter would be best choice in the interrupting condition of i=50 kA and arcing time of 1.35 cycle.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.