Abstract

Two-phase pressure drop characteristics of refrigerant-oil mixture in circular tubes filled with metal foam were experimentally investigated. Experimental conditions cover nominal oil concentrations from 0% to 5%, metal foam structures of 5 PPI and 10 PPI, vapor qualities from 0.2 to 0.8, and mass fluxes from 30 to 90 kg/m2s. The test results show that the pressure drop increases with the increase of oil concentration, mass flux or vapor quality. The presence of oil increases pressure drop by a maximum of 25% and 50% for 5 PPI and 10 PPI metal foams, respectively. The enhancement effect of oil for high PPI metal foam is more evident than that for low PPI metal foam. A correlation for predicting the two-phase pressure drop of refrigerant-oil mixture in circular metal-foam tubes was developed, and it agrees with 90% of the experimental data within a deviation of ±20%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.