Abstract

This paper presents the theoretical background needed to understand the effect of the parameters that affect the ratio rho between the equivalent neutral path resistance and line resistance of a transposed three-phase line. The ratio rho has a significant impact on the value of the apparent power as defined in IEEE Std. 1459. The ratio rho, however, depends on the topology of the power network as well as the type and size of the loads supplied by the feeder on which the apparent power is measured. It was found that for a wide range of conditions rho ap R 0/R +, where R 0, R + are the zero- and positive-sequence resistances of the line supplying the observed load.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.