Abstract
An investigation has been made into the effect of oil concentration on evaporation heat transfer coefficients in refrigerant-oil mixtures flowing in a horizontal tube. A new correlation is presented for heat transfer coefficients in convective evaporation of refrigerant-oil mixtures that predicts the results of the present study within approximately ±20%. The paper reports measurements of evaporation heat transfer coefficients in refrigerants R12 and R22, both oil-free and with two concentrations of Shell Clavus 32 oil. A 1·8 m long ⅜ in O/D copper tube (8·05 mm I/D) was used, at evaporation temperatures of −5°C, 0°C and +5°C. Heat flux and mixture mass velocity were kept constant at 2500 W m−2 and 155 kg m−2 s−1, respectively, and measured coefficients were in the range of 1400 to 3900 W m−2 K−1. The results showed that, for a complete evaporator, 2% oil may be expected to increase the heat transfer coefficient by 12%, but 10% oil returns the coefficient to oil-free values.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.