Abstract

The arrangement of insulator strings has an effect on its pollution flashover characteristics. A new arrangement of insulator strings, inverted T-type arrangement, is proposed in this study. The electric field distribution is simulated and the pollution flashover characteristics are tested in an artificial climate chamber. The test results indicate that the inverted T-type arrangement can greatly improve the flashover voltage of polluted insulator strings, the ‘7 + 2’ inverted T-type arrangement can increase the flashover voltage of each insulator by 8.5% on average, and the ‘3 + 3’ inverted T-type arrangement can increase the flashover voltage of each insulator by 13.4%. The discharge process is different from that of the normal suspension string when the insulator string is inverted T-shaped, i.e. a local arc is produced at the low voltage end of the insulator string and develops downward along the suspension part. While as for the horizontal tension string parts, it is difficult to generate arc during discharge development.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.