Abstract

The refrigerant R-134a flow distributions were experimentally studied for a round header-10 flat tube test section simulating a brazed aluminum heat exchanger. Three different inlet orientations (parallel, normal, vertical) were investigated. Tests were conducted with upward flow for the mass flux from 70 to 130 kg m−2 s−1 and quality from 0.2 to 0.6. Tubes were flush-mounted in the header with no protrusion. Both for liquid and gas, the best flow distribution was obtained from vertical inlet configuration. Between other two inlet configurations, parallel inlet was better for liquid distribution, and normal inlet was better for gas distribution. In general, the effect of mass flux or quality on flow distribution was not significant. Correlations were developed to predict the fraction of liquid or gas taken off by downstream channel as a function of header liquid Reynolds number at immediate upstream. Header pressure drop was obtained by subtracting appropriate pressure drops from the measured pressure drop. The header pressure drops were mostly negative, which implied that the pressure was recovered in the header.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.