Abstract

An experimental study is conducted to investigate the effect of hydraulic diameter on the saturated flow boiling characteristics of deionized water in parallel rectangular microchannels. Experiments have been performed for the mass fluxes of 51, 65, 78 and 93 kg m−2 s−1, and the hydraulic diameters of 100, 150, 200 and 250 μm. The wall heat flux ranges from 35.9 to 105.6 kW m−2. To eliminate the effect of aspect ratio and to address clearly the effect of hydraulic diameter, all the channels are designed with square cross section. Flow visualization studies are performed for a better understanding of the underlying physical phenomena. Effects of heat flux, mass flux and vapor quality on the heat transfer and total pressure drop have been investigated, too. It is concluded that hydraulic diameter has significant influence on both of the local two phase heat transfer coefficient and the total pressure drop.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.