Abstract

At present, there is great interest in indirect evaporative coolers (IECs), which can be effectively used to increase energy efficiency of HVAC systems, with particular attention to data center applications. In such devices, performance significantly depends on the formation of an adequate water layer on heat exchanger plates. Therefore, efforts should be made to promote water spreading through an appropriate design of the system.In this study, an experimental analysis of IECs manufactured with heat exchangers having different geometry is carried out. The scope of the research is to investigate the effect of different plates protrusion and pitch on IEC wet bulb effectiveness and pressure drop. Tests are carried out with counter and parallel air and water flow arrangement.Results highlight that plates geometry influences both surface wettability and the heat transfer rate. A reticular plates protrusion appears to be a good compromise to enhance system effectiveness. Tests also highlight that the parallel water and secondary air flows arrangement leads to higher wet bulb effectiveness and lower pressure drop compared to the counter flow configuration.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.