Abstract

The refrigerant flow distribution in the parallel flow microchannel evaporators is experimentally investigated to study the effect of header configuration. Six different configurations are tested in the same evaporator by installing insertion device and partition plate in the header to ensure the consistency of the other structure parameters. The results show that the uniformity of refrigerant flow distribution and the heat transfer rate are greatly improved by reducing the sectional area of header. The heat transfer rate can increase by 67.93% by reducing the sectional area of both inlet and outlet headers. The uniformity of refrigerant flow distribution and the heat transfer rate become worse after installing the partition plate in the insertion devices and changing the inner structure of the header further.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.