Abstract

This study conducted experiments on the optimized fin pitch for crimped spiral fin-and-tube heat exchangers. The experiments covered a size range of 2.4–6.5mm, which is the manufacturing limitation for this kind of fin. The water-flow arrangement used in this experiment combined the parallel cross-flow and the counter cross-flow in a two-row configuration. Ambient air was used as the working fluid on the air-side, and hot water was used on the tube-side. The effects of fin pitches on the heat transfer coefficient and pressure drop characteristics were studied. The results clearly showed that the convective heat transfer coefficient (ho) for a fin pitch of 2.4mm is relatively low compared with that of other fin pitches with the same air frontal velocity. Using larger fin pitches (i.e., 4.2, 6.2, and 6.5mm) resulted in negligible differences in the pressure drop. Moreover, this work introduces the parameter of three performances indexes, which can be expressed as the ratio of the desired output to the required input, for optimization purposes. Due to the difference in optimum fin pitch obtained by these performance indexes, an intersection analysis was conducted. The results indicated that the optimum fin pitch is 4.2mm for this work, which could be valuable for the effective design for industrial thermal-system applications.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.