Abstract

This paper presents a technique to determine the effect of the field-voltage circuit during the load-rejection test of a large-rating salient-pole synchronous generator. Once the circuit powered by a six-pulse converter connected to the excitation transformer of the generator unit corresponds to a power-supply voltage not constant immediately after the load rejection, a careful evaluation of the resulting signals is necessary to extract rotor and stator parameters from the comparison with theoretical expressions derived under the assumption of constant-field terminal voltage and excluding external effects. The results obtained in the load-rejection test of a 179-MVA, 13.8-kV generating unit at Nova Ponte power plant show the parameters that are more affected by the external impedance in series with the rotor circuit and how to compensate them.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.