Abstract
As it is known there are many factors affecting underground power distribution cables loadings. Such these factors are ambient temperature, cable depth laying, and number of cable parallel circuits and thermal resistivity of the soil. One important factor usually ignored is the formation of dry zones around the underground power cables due to cable loading. Dry zones are usually formed around underground power cables under loading condition due to the migration of soil moisture content. In this paper the effect of dry zone formation on the underground power cables ampacity is investigated. De-rating factor for the formation of dry zone around underground power cables is suggested and calculated for different types of natural backfill soils. IEC 60287-1-3 is taken as reference. Experimental work is done to study the dry zone phenomena of each type of soil.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.