Abstract

An experimental investigation is performed to study the friction factor ( f ) and convection heat transfer coefficient (h) behavior in an asymmetrically heated equilateral triangular duct by using delta–winglets vortex generators which are embedded in a turbulent boundary layer. Two side walls of the heated test section are electrically heated with a constant heat flux, whereas the lower wall is indirectly heated. Reynolds number (Re) is ranged from (23,000) to (58,000). Two sizes and three attack angles of vortex generators are studied here for three cases; single, double, and treble pairs of generators. Each pair was supported in one wall of the test section at the various locations from the leading edge. The indicated results that friction factor ( f )and Nusselt number (Nu) are relatively proportion with the size, number and the inclination angle of the generators. The ( f ) decreases as airflow rate increases whereas Nu number increases. The present data of ( f ) is less than the data of Chegini by about (6.5 %) and overpredicts the data of Altemani by about (1.7 %).

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.