Abstract

Corrosion inhibitors can affect calcium carbonate precipitation and associated in situ and in-service water distribution pipeline leak repair via clogging. Clogging of 150 μm diameter leak holes represented by glass capillary tubes, in recirculating solutions that are supersaturated with calcite (Ωcalcite = 13), demonstrated that Zn, orthophosphate, tripolyphosphate, and hexametaphosphate corrosion/scaling inhibitors hinder clogging but natural organic matter (NOM) has relatively little impact. Critical concentrations of phosphates that could inhibit leak repair over the short-term in one water tested were: tripolyphophate (0.05 mg/L as P) < hexametaphosphate (0.1 mg/L) < orthophosphate (0.3 mg/L). Inhibitor blends (Zn+orthophosphate and Zn+NOM+orthophosphate) had stronger inhibitory effects compared to each inhibitor (Zn, orthophosphate or NOM) alone, whereas Zn+NOM showed a lesser inhibitory effect than its individual component (NOM) alone due to formation of smaller CaCO3 particles with a much more negative zeta-potential. Overall, increased dosing of corrosion inhibitors is probably reducing the likelihood of scaling and in-service leak repair via clogging with calcium carbonate solids in potable water systems.