Abstract

This study analyses quantitatively the effect of circulating current's amplitude and phase on the input line current of 12-pulse rectifier with active inter-phase reactor. The input line current and its total harmonic distortion (THD) are calculated under different amplitudes and phases of circulating current, and according to the calculation results, the effect of circulating current is analysed. Different from the previous results, it is obtained that the system has better performance when the amplitude of circulating current is slightly less than, but not equal to the half of load current. Both phase lagging and leading increase the THD of input line current. Some simulation and experiment are carried out to validate the theoretical analysis.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.