Abstract

AbstractThe extinction of the partial discharge (PD) pulse has frequently been observed in an epoxy specimen with a closed void during voltage endurance tests using a CIGRE Method‐II electrode. The individual discharge pulse becomes so small that the discharges cannot be detected by conventional pulse detection methods. Such discharges are known as “swarming pulsive microdischarges” (SPMD).In this paper, the SPMD characteristics are investigated by varying the frequency of the applied voltage from 0.1 to 240 Hz. As a result, the SPMD are found to occur less frequently as the frequency is lowered. To seek this cause, one‐shot voltages were applied repeatedly at constant intervals. By varying the interval from 0.02 to 100 s, the PD off an electrically aged specimen was measured. It was revealed that the discharge magnitude increases as the interval becomes longer. The onset of SPMD was found to depend on the preceding discharge. The results explain the reason why swarming is harder to occur at lower frequency with a longer discharge interval. Hence, in the conventional pulse detection, it is useful to employ the very low frequency for diagnosis of machine insulation containing enclosed voids.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.