Abstract
Fixed plate enthalpy heat exchanger which utilizes permeable material as heat and moisture transfer surface has been used as an energy recovery system to recover sensible and latent heat in HVAC systems. The heat exchanger effectiveness is affected by the air flow profile. It is well known that counter flow configuration provides highest effectiveness, however, in real applications, it is not possible to implement a counter flow configuration, as both inlet and outlet ducts of the two flow streams are located on the same side of the heat exchanger. Therefore, several quasi-counter-flow heat exchanger designs including Z-shaped, L-shaped, Z-shaped opposite flow configurations are proposed in this research and their effect on energy consumed by an air conditioning cooling coil has been investigated, where each of the proposed heat exchanger is incorporated in an air conditioning cooling coil model. The modeled cooling coil energy consumption and energy recovered by the heat exchangers are evaluated under Kuala Lumpur weather conditions. It has been found that an air conditioner coupled with L-shaped heat exchanger recorded up to 20% increase in energy recovery in comparison with Z-shaped oposite and Z-shaped heat exchanger.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.