Abstract

In this study, effect of air change rate (air change per hour – ACH) on indoor particle dispersion and deposition in a ventilated room is investigated. A reduced-scale model is designed to conduct experiments. Numerical predictions are performed by using the commercial software ANSYS Fluent 16.0. Four different values of the air change rate (1.73, 2.88, 5.76 and 7.68) and five different values of the particle diameter (0.181, 2.188, 4.42, 8.89 and 17.8 μm) are considered. Constant particle flow rate and proportional particle flow rate with inlet velocity cases are examined comparatively. Results show that, except from some inconsistencies for the largest particle diameter due to the accumulation and outlet opening location, the contaminant level decreases with increasing air change rate for a constant value of the particle flow rate while an opposite trend is observed for the proportional particle flow rate case.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.