Abstract
This study analyses economic benefits of an air-cooled chiller retrofitted with advanced heat rejection features. The rated capacity was 282 kW and operating variables were monitored comprehensively to develop random forest models. The top five variables to ensure model accuracy were identified. Electricity savings were predicted by the models with 3 advanced operating modes: variable speed control for condenser fans with an adjustable condensing temperature (the VSD mode), mist precooling of condenser air (the Mist mode), and their composites (the VSD + Mist mode). The integrated part load value (IPLV) was 2.90, 3.31, 2.93 and 3.34 for the normal mode, VSD mode, Mist mode, and the VSD + Mist mode, respectively. For a chiller system serving an office building, the VSD mode gave the highest economic benefit with a simple payback of 10.83 yrs and an internal rate of return of 4.38% over a 15-yr life cycle.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.