Abstract

Multi-story, old reinforced concrete (RC) structures with a “soft-story” on the ground floor, sustain considerable damage to the soft story during earthquakes due to the presence of masonry infills in the upper stories. Aspects of such masonry infill–RC frame interaction are briefly discussed and a particular retrofitting scheme for the soft story is studied. It consists of RC infills, added within the bays of the ground floor frames and combined with RC jacketing of the surrounding frame, aiming to avert such soft-story deficiency. The impact of such a retrofit is studied through the measured response of 1/3 scaled single-story, one-bay frames subjected to cyclic seismic-type horizontal loads. It is shown that this retrofit results in a considerable beneficial increase in stiffness, strength, and plastic energy consumption. The importance of the presence of effective steel ties connecting this RC infill with the surrounding frame is also demonstrated. In order to achieve these desired beneficial effects to such vulnerable buildings, additional design objectives are established with the aim of avoiding premature failure of the RC infill panel and/or fracture of the steel ties and to protect the surrounding RC frame from undesired local damage. A numerical methodology, which is validated by using the obtained experimental results, is shown to be capable of predicting reasonably well these important response mechanisms and can therefore be utilized for design purposes.