Abstract

In the impartial factor ungrounded system, ferromagnetic resonance overvoltage is a frequent fault that lasts for a lengthy time and is hazardous to the grid. In this paper, the mechanism of grid ferromagnetic resonance overvoltage is first explored in depth. The precept of impartial voltage shift and ferromagnetic resonance brought about through PT saturation is analyzed with the aid of graphical and mathematical analysis. Then, the characteristics of fault current information are extracted by wavelet transform, and indicators such as wavelet fault degree, wavelet singularity and wavelet energy measurement are obtained respectively. D-S evidence theory is used to fuse multi-source information of electrical volume and switching quantity, so as to obtain comprehensive fault results of power grid more accurately. Finally, based on the time series risk assessment, the distribution network time series risk index is calculated, the risk level and risk area of each period are determined, and the early warning results are issued. Finally, an example is given to verify the effectiveness of the proposed method.