Abstract

Abstract Measurement-based real-time voltage stability assessment methods typically use a Thevenin Equivalent (TE) model. The TE is computed under the assumption that all generators and loads seen from an individual load-bus are constant during the time-window when measurements are obtained. This assumption does not hold in actual power systems. In fact, load changes at other load-buses result in variations on the voltage of a single-port equivalent model of the power system as seen from a load-bus. To consider these variations, this paper uses an interpolation method to develop a dynamic TE model from synchrophasor measurements, which is suitable for measurement-based real-time voltage stability assessment. In addition, a reduced network model is proposed to separate and quantify the impact of other loads and generators on the voltage stability of an interested load-bus in networks without full observability. The proposed method has been assessed through various simulation scenarios, and illustrated using actual field measurements.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.