Abstract

For corroded piping in low temperature systems, such as service water systems in nuclear power plants, replacement of carbon steel pipe with high density polyethylene (HDPE) pipe is a cost-effective solution. HDPE pipe can be installed at much lower labor costs than carbon steel pipe, and HDPE pipe has a much greater resistance to corrosion. This paper presents the results of the seismic testing of selected vent and drain configurations. This testing was conducted to provide proof of the conceptual design of HDPE vent and drain valve configurations. A total of eight representative models of HDPE vent and drain assemblies were designed. The models were subjected to seismic SQURTS spectral acceleration up to maximum shake table limits. The test configurations were then checked for leakage and operability of the valves. The results for these tests, along with the test configurations, are presented. Also presented are the acceleration data observed at various points on the test specimens.