Abstract

Through support of the US Department of Energy’s Office of Basic Energy Sciences, Oak Ridge National Laboratory has begun applying machine learning methods to improve accelerator and target performance of the Spallation Neutron Source (SNS). These methods are being applied to the control optimization and power upgrade of the SNS Cryogenic Moderator System (CMS). A numerical model of the CMS has been developed to study these optimizations and system modifications using EcosimPro. This paper compares steady-state and transient numerical results with experimental data. Control optimization studies focused on dampening mass flow, temperature, and pressure fluctuations during sudden losses of accelerator beam power. This analysis was conducted by adjusting five proportional-integral-derivative controllers connected to four flow control valves and one heater. Future efforts include power uprate studies focused on increasing the CMS cooling capacity. The current accelerator power is 1.4 MW; the first target station is being upgraded to 2.0 MW as part of the Proton Power Upgrade effort. The CMS cooling capacity is sufficient for 2.0 MW operation.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.