Abstract

A Kalman filter is used to obtain the optimal estimate of the power system harmonic content. The measurements are simulated by adding Gaussian noise to the power system voltage and line flows at different harmonies obtained from a harmonic load flow program (HARMFLO). The effect of load variation over a one day cycle on the power system harmonics and standard are presented. The test results on the IEEE 14 bus system are included. The main difference in this approach from static estimation methods is that this method is dynamic and has the capability of tracking harmonic content versus time. >

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.