Abstract

Multi-unit air conditioners (MUACs) are widely used in light commercial buildings and residential buildings due to their higher thermal comfort and energy efficiency. To investigate the transient characteristics of MUACs, a dynamic simulation model with the framework of two-phase fluid network is developed. The state-space forms are used to model the system and components, and the component submodels are embedded in the fluid network model, which makes it possible to update the system model and components submodels independently. In the model of state-space form, the differentials are obtained by taking the inverse of coefficient matrix, and then the state parameters are calculated by integrating the differentials with time. The simulation outputs are compared with the experimental data in the step changes of the compressor speed and electronic expansion valve openings. The comparison shows that the proposed model can catch the dynamic characteristics of MUACs with high accuracy. Therefore, it can be used as an effective tool to analyze the transient performance and optimize the control algorithm of MUACs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.