Abstract

In this study, some locations with different climates, off-grid zero energy buildings with hydrogen energy storage systems are designed, and transient analysis is conducted. These considered buildings supply their electricity consumption without using the electrical grid and PV panels or wind turbines. Also, they supply thermal comfort to occupants by using a vapor compression chiller and humidifier. Domestic hot water of occupants is supplied using solar collectors. For analyzing building's performance and objectives achievement, TRNSYS software is used. Also, for evaluating occupant thermal comfort, the Fanger model is used. The considered building is a one-story building with a 150 m2 area. Four occupants are considered. Both of them are seated at rest, and another is seated with light working such as typing. Using the Fanger model equation and MATLAB software, the thermal comfort of occupants is determined. For domestic hot water consumption, verified profiles that vary during 24 h of the day are considered. Achieved results show that for humid and cold cities, PV panels with an area of 73 and 76 m2 can be supplied the required electricity of considered building with four occupants and battery state of charge is higher than 50% and 10%, respectively. Moreover, with a suitable air conditioner system, the predicted percentage of dissatisfied (PPD) can be lower than 12% and 8% for humid and cold cities. Therefore, the building can be converted to a zero-energy building using its rooftop area.