Abstract

Five energy management control (EMC) functions such as outside air (OA) economizer cycle, programmed start and stop lead time, load reset and occupied time adaptive control strategy are developed and evaluated using a variable air volume heating, ventilating and air conditioning, VAV-HVAC, system level dynamic model as a simulation platform. A real time system embedded with the above EMC functions is presented. The simulation results manifest that energy savings of 17% can be achieved when the system is operated with the EMC functions and optimal set points compared with the system without such functions. These results do point out that the optimal set point strategy is very useful in achieving energy efficient operation of HVAC systems.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.