Abstract

the Main Cause of Substation Circuit Breaker Break Accidents Mainly in Post Insulator Accidents is That the Flexural Strength of the Insulators Does Not Meet the Design Requirements. At the Same Time, There Are Problems Such as Eccentricity of the Porcelain Column, Large Difference in the Thickness of the Cement Casting, No Asphalt Buffer Layer in the Pouring Part, and No Waterproof Silicone Rubber. as the Temperature Changes, a Break Occurs under the Mechanical Force of the Switch. This Paper is Based on the Dynamic Simulation and Optimization of the Structure of High Voltage Circuit Breaker Based on the Finite Element Partial Dynamic Characteristics of Mechanical Structure. through Experiments by Ansys, the Optimized Solution Helps Manufacturers to Improve the Manufacturing Process of Insulators. the Operating Unit Strengthens the Equipment Acceptance, Operation, and Maintenance, and Carries out Visual Inspection and Ultrasonic Flaw Detection in Strict Accordance with the Requirements of the Regulations, Which Can Prevent the Occurrence of Insulator Breakage Accidents.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.