Abstract

In this paper, the basics of dynamic phasor (DP) modelling has been introduced by employing a simple RL-series circuit. In the example, the actual time-domain simulation and the DP-based simulation are presented in addition to the eigenvalue analysis of the RL-circuit in the DP-domain. With this introduction, following a systematic procedure, the DP-model of a static VAr compensator (SVC) which involves periodic switchings, is derived. To verify this model, a case study with an SVC in the IEEE first benchmark system for subsynchronous resonance (SSR) study has been simulated. The simulation results are also compared with those obtained using a susceptance model for SVC. A PSCAD/EMTDC-based detailed simulation demonstrated that the DP-model offers good-enough accuracy with much less computational effort.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.